2.5 kW Battery Charger


2.5 kW Battery Charger

Specification No. EDTS-415 REV-0

Description :

Technical Specifications :

Type
Constant Voltage Naturally cooled, IGBT/SiC based, DSP controlled
Input Voltage
Nominal Voltage 415 V AC, 3-phase, 3-wire system
Operating Voltage & Frequency Range 415 V ±15%, 50 Hz ±3%
Total Harmonic Distortion (THD)
Voltage THD < 10%
Output (DC)
Isolation Fully insulated from coach body on both positive and negative sides; galvanic isolation between input & output
Output Voltage 122 V DC ±2%
Output Current 20 A (max.)
Battery Compatibility 110 V, 70 Ah VRLA type
Output Power 2.5 kW (max.)
Efficiency > 90%
Ripple Content < 2% of set Voltage and < 3% of set Current
Protections
Output Over-Voltage Trip 136 V DC ±2 V
Output Current Limit Limited to 20 A
AC Under/Over-Voltage Protection Trips at 350 V ±5 V (under) and 480 V ±5 V (over); auto-restart when input is > 355 V or < 475 V
Withstand Capability Withstands 510 V AC for 2 minutes without damage
Self-Reset Feature Automatic restart once trip condition normalizes
Earth Leakage Detection Trip provided
Ingress Protection IP-67 (dust and water protection)
Output Short-Circuit Protection Trip provided
Reverse Polarity Protection Provided in battery circuits
Overload Protection 22 A for 1 minute
Mechanical
Weight < 75 kg